The Series MSX Magnesense® Differential Pressure Transmitter combines the stability and versatility of the original Series MS2 Magnesense® II Transmitter for use in building control applications. The MSX simplifies the ordering process to deliver the desired configuration,Which reduces product setup time.Pressure ranges are available in Pa,mm w.c.,and in w.c.All pressure ranges can be configured in unidirectional or bidirectional modes, providing a total of 32 ranges.The MSX Transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability for calculating flow. Dual voltage and milliamp output signals can be used to provide both control and Equipment Output signal verification.

Model Description
MSX-U12-IN Universal (Duct Or Wall) Mount, universal current/volt outputs, uni-directional,Range 2 (1,2,3, 5″ wc)
MSX-U12-IN-LCD Universal (Duct or Wall) Mount, Universal current/volt outputs, uni-directional,Range 2 (1,2,3, 5″ wc) with LCD Display
MSX-W10-IN Wall Mount,Universal current/voltage outputs,Uni-directional,Range 0 (0.1,0.15, 0.25,0.5″ wc)
MSX-W10-IN-LCD Wall Mount,Universal current/voltage outputs,Uni-directional,Range 0 (0.1,0.15, 0.25,0.5″ wc) with LCD Display
MSX-W10-PA Wall Mount,Universal current/voltage outputs,Uni-directional,Range 0 (60,75, 100,125″ Pa)
MSX-W11-IN Wall Mount,Universal current/voltage outputs,Uni-directional,Range 1 (0.1, 0.25, 0.5, 1″ wc)
MSX-W11-IN-LCD Wall Mount,Universal current/voltage outputs,Uni-directional,Range 1 (0.1,0.25, 0.5, 1″ wc) with LCD Display
MSX-W12-IN Wall Mount,Universal current/voltage outputs, uni-directional,Range 2 (1,2,3,5″ wc)
MSX-W12-IN-LCD Wall Mount,Universal current/voltage outputs, uni-directional,Range 2 (1,2,3,5″ wc) with LCD display
MSX-W12-PA Wall Mount,Universal current/voltage outputs,Uni-directional,Range 2 (600,750, 1000,1250″ Pa)
MSX-W13-IN Wall Mount,Universal current/voltage outputs,Uni-directional,Range 3 (10,15,25, 28″ wc)
MSX-W13-IN-LCD Wall Mount,Universal current/voltage outputs,Uni-Directional,Range 3 (10,15,25, 28″ wc) with LCD Display
MSX-W13-PA Wall Mount,Universal current/voltage outputs,Uni-Directional,Range 3 (3000, 4000,5000,7000″ Pa)
MSX-W20-IN Wall Mount,Universal Current/Voltage outputs,Bi-directional, range 0 (0.1,0.15, 0.25,0.5″ wc)
MSX-W20-IN-LCD Wall Mount,Universal current/voltage outputs,bi-Directional,Range 0 (0.1,0.15, 0.25,0.5″ wc) with LCD Display
MSX-W20-PA Wall Mount,Universal current/voltage outputs,Bi-Directional,Range 0 (60,75, 100,125″ Pa)
MSX-W21-IN Wall Mount,Universal current/voltage outputs,Bi-directional, range 1 (0.1,0.25, 0.5,1″ wc)
MSX-W22-IN Wall Mount,Universal current/voltage outputs,Bi-Directional,Range 2 (1,2,3,5″ wc)
MSX-W22-IN-LCD Wall Mount,Universal current/voltage outputs,bi-directional,Range 2 (1,2,3,5″ wc) with LCD display
MSX-W22-PA Wall Mount,Universal current/voltage outputs,bi-directional, range 2 (600,750, 1000,1250″ Pa)
MSX-W23-IN Wall Mount,Universal current/voltage outputs,Bi-directional,Range 3 (10,15,25, 28″ wc)

SPECIFICATIONS

  • Service:Air And Non-Combustible, Compatible Gases.
  • Wetted Materials:Consult factory.
  • Accuracy:±1% FSO.
  • Stability:±1% FSO/year.
  • Temperature Limits:-4 to 158°F (-20 to 70°C).
  • Pressure Limits:Ranges 0 and 1: 3.6 psi (24.8 kPa) max operation, 6 psi (41.3 kPa) burst; Ranges 2, 3 and 4: 6 psi (41.3 kPa) max operation, 6 psi (41.3 kPa) burst.
  • Power Requirements:10-36 VDC (2-wire), 17-36 VDC or isolated 21.6-33 VAC (3-wire).
  • Output Signals:4-20 mA (2-wire); 0-10 V or 0-5 V selectable (3-wire).
  • Response Time:Instantaneous (default) or 3 s (selectable).
  • Zero and Span Adjustments:Digital push-button.
  • Loop Resistance:Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 k Ω.
  • Current Consumption:21 mA max continuous.
  • Electrical Connections:4-wire removable European style terminal block for 16 to 26 AWG.
  • Electrical Entry:1/2″ NPS thread.
  • Display (optional):4 digit LCD.
  • Process Connections:1/8″, 3/16″, 1/4″, 5 mm, and 6 mm ID flexible tubing.
  • Enclosure Rating:NEMA 4X (IP66), UL 2043 (Plenum), UL94 V-0.
  • Mounting Orientation:Pressure sensor measurement unaffected by orientation.
  • Weight:8.0 oz (230 g).
  • Compliance:CE.

FEATURES

  • Read LCD values easier with rotatable 180° display
  • Quick and easy wiring via the optional toolless terminal block
  • Add safety to variety of applications with UL94 V-0 and plenum ratings

 

 